Description
Standards
International : HD 603 S1/3FNational : SFS 4880
Description
AMCMK is a lead free, PVC insulated, PVC sheathed cable with sector shaped, stranded aluminium conductors. The cable has a screen of annealed copper wires with opposite open helix of copper. AMCMK is designed according to HD 603. The conductors have resistance and number of wires according to IEC 60228 class 2. The cores are identified by colours according to HD 308. The sheath is marked type/manufacturer/year+month/metre marking. AMCMK meets the requirements for flammability class according to IEC 60332-3 (F4B). The cable is certified by SETI.
Lifemark(TM) recycling marking
The external surface of the outer sheäth is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.
Standards
AMCMK is manufactured and tested according to SS 424 14 18. The cable can be loaded in accordance with national regulations on electrical installations.
Certification
Certified by SETI.
Quality system
Designed, manufactured and tested in accordance with ISO 9001.
Environmental management system
The activities at our plant in Grimsås are certified to ISO 14001.
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Aluminium |
| Conductor flexibility | Stranded class 2 |
| Conductor shape | Sector-shaped |
| Insulation | PVC |
| Outer sheath | PVC |
| Colour | Black |
| Lead free | Yes |
| Dimensional characteristics | |
| Number of cores | 4 |
| Conductor cross-section | 240mm² |
| Average insulation thickness | 2.2mm |
| Screen section | 72mm² |
| Average sheath thickness | 2.9mm |
| Nominal outer diameter | 59.0mm |
| Approximate weight | 510.0kg/100m |
| Electrical characteristics | |
| Max. DC resistance of the conductor at 20°C | 0.125Ohm/km |
| Resistance of the screen | 0.25Ohm/km |
| Nominal inductance | 0.18mH/km |
| Rated Voltage Uo/U (Um) | 0.6/1 kV |
| Usage characteristics | |
| Minimum installation temperature | -15°C |
| Maximum operating temperature | 70°C |
| Short-circuit max. conductor temperature | 150°C |
| Length | 500m |
| Laying operation bending radius | 472mm |
| Minimum static operating bending radius | 590mm |
| Packaging | K22 |
| Flame retardant | IEC 60332-3 Cat. B |